초록

The public relations room of the waste disposal facility is a space that can be visited by a large number of unevaluated personnel. Therefore, it is essential to design against fire, and research on fire and evacuation is essential. In this study, in order to evaluate the safety of the occupants in the event of fire and evacuation based on the life safety standards of occupants, the increase in risk due to heat, visible distance, and toxic gases on a plane 1.8m from the floor, which is the limit of breathing of the evacuee, over time. It was analyzed by location. As a result, the RSET of the P-01 exit was 93.0 seconds and the ASET was 272.6 seconds, the RSET of the P-02 exit was 45.8 seconds, the ASET was 147.7 seconds, the RSET of the P-03 exit was 106 seconds, and the ASET was 182.9 seconds.

목차
Abstract
1. 서 론
2. 판정 기준
    2.1 화재 시뮬레이션 평가 방법
    2.2 피난 시뮬레이션 평가 방법
    2.3 피난 안전성 평가 방법
3. 수치해석 결과 및 분석
    3.1 화재 시뮬레이션
    3.2 화재 시뮬레이션 결과
    3.3 피난 시뮬레이션
4. 결 론