The nuclear accident due to the recent earthquake in Japan has triggered awareness of the importance of safety with regard to nuclear power plants (NPPs). An earthquake is one of the most important parameters which governs the safety of NPPs among external events. Application of a base isolation system for NPPs can reduce the risk for earthquakes. At present, a soil-structure interaction (SSI) analysis is essential in the seismic design of NPPs in consideration of the ground structure interaction. In the seismic analysis of the base-isolated NPP, it is restrictive to consider the nonlinear properties of seismic isolation devices due to the linear analysis of the SSI analysis programs, such as SASSI. Thus, in this study, SSI analyses are performed using an iterative approach considering the material nonlinearity of the isolators. By performing the SSI analysis using an iterative approach, the nonlinear properties of isolators can be considered. The difference between the SSI analysis results without iteration and SSI with iteration using SASSI is noticeable. The results of the SSI analysis using an effective linear (non-iterative) approach underestimate the spectral acceleration because the effective linear model cannot consider the nonlinear properties of isolators. The results of the SSI analysis show that the horizontal response of the base-isolated NPP is significantly reduced.
본 연구에서는 진동대 실험을 통한 수계형 소화설비의 내진성능평가를 실시하였다. 실험에 사용된 수계형 소화설비 시설에는 일반 배관, 내진형 배관, 펌프 등 이다. 그리고 수계형 소화설비 시설의 동적거통특성을 파악하기 위하여 El-Centro 지진파 50%,70%, 100%, 120% 수준의 가진을 가하였다. 그 결과, 내진형 설비보다 일반형 설비에서 변위 응답과 가속도 응답이 큰 것으로 보아내진형 설비가 일반설비에 비해 내진성능이 우수하다는 것을 알 수 있었다. 또한, 가진 수준별 가속도 응답스펙트럼을 통하여 일반형시설과 내진형 시설의 성능 평가뿐만 아니라 작은 규모의 지진에서도 일반형 설비의 파괴가 일어날 수 있다는 것을 알 수 있었다. 본연구를 통해 수계 소화설비의 내진성능을 평가 할 수 있었고 수계 소화설비의 내진성능 기준을 검증할 수 있었다.