MCCI, one of the ex-vessel phenomena during a severe accident, is generally caused by mutual reactions between molten core and reactor building basemat concrete, but occurs between sacrificial materials made by concrete and corium in APR nuclear power plant with PECS applied. In this paper, MCCI analysis was performed to design and apply a device to block the core melt at the junction connected to the ICI cavity sump from the core catcher installed in the reactor cavity of the APR. Unlike the sacrificial material, which has a cooling effect by inducing erosion of the ex-vessel core melt, the device is composed of concrete applied as a barrier to protect the ICI cavity sump. The decent thickness of the barrier wall of the device was calculated.