Currently, the number of a shopping center building is increasing because most people want to go a shopping center building easily for buying many things and eating some foods. That are a normal trend these days. However, the increasing number of shopping center buildings has been increasing the number of shopping center building fires which also have been making social problems. Therefore, this study was conducted for the fire department connection among other fire facilities because it is important for fire suppression. The research subject is on the fire department connections that are on 70 shopping center buildings of more than 5 years old constructed. Survey and analysis were conducted for 70 fire department connections. The result of this study is that all installed fire department connections have a type that includes one or two holes each at 65mm wide, and the average distance between fire department connections and access roads is 4.85m. The total average percentage of insufficiency conditions such as drive ways for fire trucks, visibility, accessibility, pressure range sign, installed height, cover of the hole, etc. is 45.3%. So improvement of law and systems, that are fire facility construction and maintenance implementations, will be needed in my opinion.
본 연구에서는 소방시설 중 화재진압에 중요한 역할을 하는 연결송수관설비 송수구 를 대상으로 하였다. 그리고 조사는 아파트에 설치된 60개의 송수구를 조사 및 분석을 실시하여 다음과 같은 결론을 얻을 수 있었다. 조사결과 소방차 전용도로 확보 및 접근성, 설 치높이, 압력범위표시 표지, 이물질방지 마개부착 등이 미흡하게 나타났다. 따라서 소방시설 설계, 시공, 감리를 개선하고 또한 주기적인 유지관리점검이 양호하게 될 수 있도록 제도적 개선이 필요 하다고 판단된다.