This research presents that seismic performance of steel moment resisting frame building designed by past provision(UBC, Uniform Building Code) before and after retrofitted with BRB (Buckling-Restrained Brace) was evaluated using response modification factor(R-factor). In addition, the seismic performance of the retrofitted past building was compared with that specified in current provision. The past building considered two different connections: bilinear connection, which was used by structural engineer for building design, and brittle connection observed in past earthquakes. The nonlinear pushover analysis and time history analysis were performed for the analytical models considered in this study. The R-factor was calculated based on the analytical results. When comparing the R-factor of the current provision with the calculated R-factor, the results were different due to the hysteresis characteristics of the connection types. After retrofitted with BRBs, the past buildings with the bilinear connection were satisfied with the seismic performance of the current provision. However, the past buildings with the brittle connection was significantly different with the R-factor of the current provision.
초과강도계수와 연성계수는 현행 내진기준에서 사용되는 반응수정계수를 결정하기 위한 두 가지 중요한 계수이다. 본 논문에서는 다양한 층수 및 경간을 갖는 역V형 특수 중심가새골조의 비선형 정적 해석을 수행하여 초과강도계수와 연성계수를 구하고 이를 이용하여 반응 수정계수를 산정하였다. 해석결과에 따르면 저층 구조물의 경우 IBC-2000에서 제시한 값보다 큰 반응수정계수 값을 가지며, 중층 이상의 경우 기준에서 제시한 값보다 작은 값으로 나타났다. 또한 초과강도계수와 연성계수는 구조물의 높이가 감소할수록, 스팬의 길이가 증가할수록 증가하는 것으로 나타났다.