This study analyzed and identified various causes of caustic alarms of 163 fire detectors that occurred from January 2019 to December 2021 at domestic semiconductor manufacturing plants equipped with about 30,000 fire detectors, and proposed a new non-fire prevention cause investigation plan by applying the NFPA 921 scientific methodology. The results of the study are as follows. First, in terms of necessary recognition and problem definition, an analog detector and an integrated monitoring system were proposed to quickly determine the location and installation space information of the fire detector. Second, in order to prevent speculative causes and errors in various analyses in terms of data analysis and hypothesis establishment, non-fire reports were classified into five by factor and defined, and the causes of occurrence by factor were classified and proposed. Finally, in terms of hypothesis verification and final hypothesis selection, a non-fire prevention improvement termination process and a final hypothesis verification sheet were proposed to prevent the cause from causing re-error.
The research on improvement of false alarm from the automatic fire detection system has been continually achieved in the meantime. But the research for the code-transmitter as one of component devices of the automatic fire detection system. In order to improve difficulty of the code-transmitter check-up, introduction for the address type-code-transmitter and the automatic recovery system for check up of the code-transmitter was proposed. In order to prevent against occurrence of noise and signal attenuation, introduction of the optical fiber cables that noise and signal attenuation do not occur and introduction for an optical communication relay that can apply to was proposed respectively.
The automatic fire detection system is an important facility installed with focusing on minimizing the damage from a fire. This paper presents in the followings as the methods to reduce the false alarm of the automatic fire detection system; first, to prepare for legal standard so that revised legal standard can be applied to the fire fighting property prior to revision; second, to introduce the performance based fire detection protection design in the law based fire protection design; third, to maintain the wiring of worn-out detector; forth, to introduce an evaluation system to the education for the fire warden; fifth, to extend the standard of MTBF(meantime between failure) of the detector; sixth, to extend of installing the analog type detector; seventh, to improve the structure of reset switch.