검색결과

검색조건
좁혀보기
검색필터
결과 내 재검색

간행물

    분야

      발행연도

      -

        검색결과 9

        1.
        2021.12 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this paper, a heat exchange system using cooling dehumidification and mixing process was proposed as an experimental study for a white smoke reduction heat exchanger system under winter condition. The white smoke reduction heat exchange system is divided into an EA part, SA part, W part and mixing zone. For the operating conditions, three types (Cases 1, 2, and 3) were selected depending on whether EA fan, SA fan, and A-W heat exchanger were operated. In addition, in order to visualize the white smoke exhausted from the mixing zone, it was photographed using CCTV. In order to investigate the performance of the white smoke reduction heat exchange system, the temperature reduction rate and absolute humidity reduction rate of EA and the heat recovery rate of W were calculated. The temperature change of EA and SA according to operating conditions was most effective in Case 3, and the temperature and absolute humidity at the outlet of the mixing zone were greatly reduced. From the results of the white smoke visualization, it was confirmed that the white smoke generation mechanism was different depending on the operating conditions, and the amount of white smoke generation was greatly reduced.
        4,000원
        2.
        2019.12 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this study, a white smoke reduction simple prediction model of white smoke reduction heat exchange system was developed by using EES. In order to verify the reliability of the EES model, it was compared with the computational results. The developed EES predictive model was used to calculate the temperature and absolute humidity of the mixed SA and EA according to the change of cooling water capacity, flow rate ratio of SA/EA, and SA inlet temperature. The difference between final temperature and absolute humidity at the outlet of the mixer calculated by computational analysis and EES was within 1.4% and 3.6%. As the cooling water capacity and the inlet flow rate ratio increased, and as the inlet air temperature decreased, the temperature and absolute humidity of the mixer decreased. The most influential factor in the white smoke reduction effect among the design variables of the white smoke reduction heat exchange system was the flow rate ratio of SA/EA.
        4,000원
        3.
        2019.08 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this study, the temperature, the absolute humidity, and the turbulent flow characteristics of exhaust air and supply air in the mixer were studied while changing the shape of the mixer of the white smoke reducing heat exchange system. Using Solidworks, the mixer of the white smoke reduction heat exchange system was created by 3-D model. Also, the mixed flow of supply air and exhaust air inside the mixer under the uniform inlet conditions was computed, using the solidworks flow simulation. Two types of improvement models were selected by using a perforated plate and a guide vane as a turbulent mixing flow control method of the mixer. The mean temperature and mean absolute humidity of the mixture were greatly decreased according to the internal shapes of Case 1, 2, and 3. The temperature difference between the inlet and outlet of the mixer Case 3 was 26℃. The exit temperature and absolute humidity reduction rates of Case 3 were 26.2% and 48.1%, respectively, compared with Case 1.
        4,000원
        4.
        2019.02 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this study, the characteristics of the heat flow on SA(supply air) side of the white smoke reducing heat exchange system according to the change of SA velocity were analyzed in the winter condition (outside temperature 0℃). Also, the mixing process of SA and the EA(exhaust air) is presented in the psychrometric chart to confirm the possibility of reducing white smoke. Solidworks flow simulation was used to analyze the heat flow on the heat exchange system under uniform conditions. As the inflow velocity of SA increased, the temperature of SA decreased due to the convective heat transfer improvement due to the active flow in SA system. And the outlet temperature and absolute humidity of the mixing zone decreased significantly. At SA velocity 7 m/s, the outlet temperature and absolute humidity decreased to about 58% and 82%, respectively.
        4,000원
        5.
        2018.12 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this study, effects of reducing white smoke at a heat exchange system for white smoke reduction were studied in the winter season. For this purpose, the heat transfer processes on the exhaust air were investigated by Solidworks. Five wave heat exchangers of air-to-air and air-to-water type were applied for the exhaust air heat recovery. The analytical condition of the exhaust air was fixed and the computational analysis was performed according to the change of SA(supply air) inlet velocities. In order to evaluate the performance of the heat exchange system for white smoke reduction, W(water)/SA recovered capacities and the temperature/ absolute humidity reduction rate were calculated. As SA inlet velocity increased, the exit temperature and absolute humidity of the mixing zone were reduced by up to about 40℃ and 0.12kg/kg respectively. Also, W/SA recovered capacities increased linearly up to about 35%.
        4,000원
        6.
        2018.06 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In the present study, the white reduction system was designed and manufactured to evaluate the performance of a heat exchange system using a wave heat exchanger. The reducing effect of white smoke and the amount of heat recovered from cooling water were investigated experimentally using the cooling and dehumidifying method. The white smoke reduction system consists of two parts; the generating part and the reducing part of white smoke. Experimental conditions on EA(exhaust air) and SW(supply water) were fixed. And the outlet temperature and absolute humidity of EA were measured according to inlet velocity of SA(supply air). The outlet temperatures and absolute humidities of EA gradually decreased as inlet velocities of SA increased. From the experimental results, we can see that the absolute humidity reduction rate of EA was max. 84%, and the heat recovery rate of SW was max. 42%.
        4,000원
        8.
        2011.12 KCI 등재 구독 인증기관 무료, 개인회원 유료
        Earth to air heat exchangers made by iron, aluminium, copper and poly-ethylene pipe for single greenhouse heating were experimented and blowers. Earth to air heat exchanger was installed by pipelines in earth tube at 70cm depths and air blower was the heating capacity 3kW/h, As the result, Temperature difference due to temperature history of the inlet and outlet air on the various type in earth tube in greenhouse showed that air temperature at the various type in earth tube, comparison tube were make no difference respectively. Under the experimental condition, heat fluxes and heating load were showed 6,800Kcal/h, 19,699kcal/h generally yield of Lactuca Sativa cultured during days of sowing 90day in greenhouse using copper pipe was 170% incleased.
        4,000원
        9.
        2003.09 KCI 등재 구독 인증기관 무료, 개인회원 유료
        본 연구에서는 온실의 온풍식 난방시스템 연통에 장착할 수 있는 폐열 회수기의 성능 개선을 목적으로 기 설계된 세 가지 열교환 장치와 기존의 장치에서 열교환 면적과 파이프의 두께 및 공기흐름 방향을 개량한 새 열교환 장치에 대해 열회수 성능을 실험적으로 비교 분석하였다. 그 결과 기존의 열 교환장치인 A형, B형 및 C형의 열회수 성능은 동일 송풍전입에서 각각 42.2%, 40.6% 및 54.4% 정도였으나 , 새로 개량된 D형은 69.2%로써 가장 현저히 높게 나타났다. 그러나 열회수용 공기의 흐름방향 변화에 따른 열회수 성능 개선효과 (A형 대비 B형)는 없는 것으로 나타나 적정 송풍기 용량이라면 직선형이 공기의 흐름방향 180˚C 굴절시키는 헤어핀형보다 효과적인 것으로 판단된다. 결국 열회수 성능은 열회수 시스템의 열교환 면적과 열교환 파이프의 두께 및 풍속에 크게 좌우되는 것으로 나타났다. 따라서, 열교환 파이프의 내구성 등 을 고려하여 기능한 한 범위 내에서 열 교환면적을 증대시키거나 열교환 파이프의 두께를 앓게 하고 풍속을 증대시키는 것이 열회수 성능 개선효과와 직결됨을 알 수 있었다. 그리고 송풍기 용량이 필요이상으로 큰 경우, 소비전력이 많게 되는 등의 문제가 있기 때문에 적정용량 및 제품의 안정성을 고려하여 선택해야 할 것으로 판단되었다.
        4,000원