        1.
        2024.12 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this study, the time to endure after conducting a test pressure test was analyzed according to the hose development length of the household hose reel indoor fire hydrant according to the apartment area. First, when the household area is 50㎡, a household hose reel indoor fire hydrant is installed inside the bathroom, and the hose is bent in a circular shape to the farthest fire point, and the test pressure is found to be inadequate only when the hose development length is 5m. When the household area of an apartment is 84㎡. It was found that the test pressure was inappropriate only when the hose deployment length was 5m with the hose bent in a circular shape to the farthest point by installing a household hose reel indoor fire hydrant inside the bathroom. When the hose deployment length was 15m, the average experimental value was 3.9 Mpa and the water pressure resistance time was 8 min. It was found that the test pressure and holding time were suitable for all of the working pressure of 0.7 Mpa, the inner diameter of the hose 25mm and 32mm, and the hose deployment length. When the installation of the hose reel indoor fire hydrant hose was 3 Mpa, the internal diameter of the hose was 25mm, 32mm, and the length of the hose deployment were all suitable.