This study proposes a steel plate retrofit method and a polyurea method to improve the structural stability and usability of a factory floor slab with a thickness of 120mm. To assess vibration changes, vibrations were measured before and after retrofit. A numerical analysis model was also developed to evaluate improvements in structural safety and usability. The natural frequency increased from 11.4Hz to 17Hz through steel plate reinforcement, confirming an increase in slab stiffness. The damping ratio increased from 2.3% to 3.2% with polyurea reinforcement, indicating improved vibration reduction. Additionally, numerical analysis modeling showed that the natural frequency increased from 13.9Hz to 16.2Hz due to the steel plate reinforcement, enhancing the dynamic characteristics of the floor slab and confirming the reliability of the analysis model.
전 세계적으로 지진발생이 빈번하고 많은 인명피해와 사회기반시설물의 피해가 발생하고 있다. 지진에 대한 보수, 보강기법에 대 한 연구가 많이 있었지만 대부분은 강성보강형태로 반복적인 하중이 구조물에 작용하면 2차적 피해가 발생할 수 있다. 따라서 강성보강이 아 닌 연성보강형태의 보수, 보강기법이 필요하다. 본 연구에서는 철근 콘크리트 기둥 부재에 적용할 수 있는 보강 공법으로써 폴리머계의 고인성 과 고연성 효과를 나타내는 경질형 폴리우레아를 내진보강용 재료로 선택하였고 재료의 열화 및 내화학적 특성에 대한 내구 성능을 평가하였 다. 내구 성능 평가는 폴리우레아의 산 환경 및 자외선 노출 시험을 실시하였고, 폴리우레아를 도포한 콘크리트의 탄산화 노출 및 동결융해 시 험을 실시하였다. 내진보강용 폴리우레아는 모든 시험을 통하여 내구성능과 저항능력이 우수한 것으로 판단되며 추후 내진 보강 재료로써 유 용하게 사용될 것으로 사료된다.
This study is to introduce the results of physical property test on the polyurea ultra rapid curing membrane according to the test method by the KS F 2622