Structures of high-rise buildings are less prone to earthquake damage. This is because the response acceleration of high-rise buildings appears to be small by generally occurring short-period ground motions. However, due to the increased construction volume of high-rise buildings and concerns about large earthquakes, long-period ground motions have begun to be recognized as a risk factor for high-rise buildings. Ground motion observed on each floor of the building is affected by the eigenmode of the building because the ground motion input to the building is amplified in the frequency range corresponding to the building's natural frequency. In addition, long-period components of ground motion are more easily transmitted to the floor or attached components of the building than short-period components. As such, high-rise buildings and non-structural components pose concerns about long-period ground motion. However, the criteria (ASCE 7-22) underestimate the acceleration response of buildings and non-structural components caused by long-period ground motion. Therefore, the characteristics of buildings’ acceleration response amplification ratio and non-structural components were reviewed in this study through shake table tests considering long-period ground motions.
Recently, an unprecedented emerging infectious disease has rapidly spread, causing a global shortage of wards. Although various temporary beds have appeared, the supply of wards specializing in infectious diseases is required. Negative pressure isolation wards should maintain their function even after an earthquake. However, the current seismic design standards do not guarantee the negative pressure isolation wards’ operational (OP) performance level. For this reason, some are not included in the design target even though they are non-structural elements that require seismic design. Also, the details of non-structural elements are usually determined during the construction phase. It is often necessary to complete the stability review and reinforcement design for non-structural elements within a short period. Against this background, enhanced performance objectives were set to guarantee the OP non-structural performance level, and a computerized tool was developed to quickly perform the seismic design of non-structural elements in the negative pressure isolation wards. This study created a spreadsheet-based computer tool that reflects the components, installation spacing, and design procedures of non-structural elements. Seismic performance review and design of the example non-structural elements were conducted using the computerized tool. The strength of some components was not sufficient, and it was reinforced. As a result, the time and effort required for strength evaluation, displacement evaluation, and reinforcement design were reduced through computerized tools.
Seismic demand on nonstructural components (NSCs) is highly dependent on the coupled behavior of a combined supporting structure- NSC system. Because of the inherent complexities of the problem, many of the affecting factors are inevitably neglected or simplified based on engineering judgments in current seismic design codes. However, a systematic analysis of the key affecting factors should establish reasonable seismic design provisions for NSCs. In this study, an idealized 2-DOF model simulating the coupled structure-NSC system was constructed to analyze the parameters that affect the response of NSCs comprehensively. The analyses were conducted to evaluate the effects of structure-NSC mass ratio, structure, and NSC nonlinearities on the peak component acceleration. Also, the appropriateness of component ductility factor (R p) given by current codes was discussed based on the required ductility capacity of NSCs. It was observed that the responses of NSCs on the coupled system were significantly affected by the mass ratio, resulting in lower accelerations than the floor spectrum-based response, which neglected the interaction effects. Also, the component amplification factor (a p) in current provisions tended to underestimate the dynamic amplification of NSCs with a mass ratio of less than 15%. The nonlinearity of NSCs decreased the component responses. In some cases, the code-specified R p caused nonlinear deformation far beyond the ductility capacity of NSCs, and a practically unacceptable level of ductility was required for short-period NSCs to achieve the assigned amount of response reduction.
최근 비구조요소의 피해사례가 증가하면서 비구조요소 내진설계에 관한 많은 연구가 진행되고 있다. 하지만 대부분의 연구는 평면 적 요소보다는 수직적 요소나 시스템적 요소를 변수로 층가속도를 평가하고 있다. 때문에 본 논문에서는 횡력저항에 많은 부분을 차 지하는 코어를 평면적 변수로 사용하여 비구조요소 내진설계를 위한 층가속도에 대해 평가하였다. 정사각형의 2축대칭의 평면에서 코어의 형태(위치 및 비중)변화에 따라 서로 다른 5개의 평면과 각 평면마다 5층, 10층, 15층, 20층의 층수를 가진 총 20개의 모델로 선 형시간이력해석을 수행하였다. 분석 결과 코어 위치에 따라 편심을 받는 평면에서는 층가속도가 최대 1.7배의 비틀림 증폭이 발생하 였고 구조물의 중층부에서 비틀림의 영향이 가장 큰 것을 확인할 수 있었다. 편심이 없이 코어의 비중만 변화한 평면에서는 주기 0.4694초를 기준으로 이하일 때는 주기가 증가할수록 층가속도가 저층부에서는 감소하고 고층부에는 증가하며, 반대로 주기 0.4694 초 이상일 때는 주기가 증가할수록 층가속도가 저층부에서는 증가하고 고층부에는 감소한다는 것을 확인할 수 있었다. 또한, 구조물 의 층수는 최대층가속도에 영향을 주지 못하는 것을 확인하였다. 핵심용어 :
In the event of an earthquake, non-structural components require seismic performance to ensure evacuation routes and to protect lives from falling non-structural components. Accordingly, the seismic design code proposes horizontal force for the design and evaluation of non-structural components. Ground motion observed on each floor is affected by a building's eigen vibration mode. Therefore, the earthquake damage of non-structural components is determined by the characteristics of the non-structural component system and the vibration characteristics of the building. Floor response spectra in the seismic design code are estimated through time history analysis using seismic waves. However, it is difficult to use floor response spectra as a design criterion because of user-specific uncertainties of time history analysis. In addition, considering the response characteristics of high-rise buildings to long-period ground motions, the safety factor of the proposed horizontal force may be low. Therefore, this study carried out the horizontal force review proposed in the seismic design code through dynamic analysis and evaluated the floor response of seismic waves considering buildings and predominant periods of seismic waves.
After the Gyeong-ju 9.12 earthquake, we found the necessity of seismic design of nonstructural element is important to reduce damages in view of properties and economic losses. This study focused on the investigation of damages including both properties and human beings. It was found that most of the damages are leaking of water pipe line, rupture of glasses, spalling of roof finishing, cracks of building, and falling from roof. It was also found that the seismic design force of nonstructural elements is taking account into the natural periods, amplification factors, response modification factors to forsee inelastic behaviors. From this studies, it is recommended that more studies are necessary on the seismic design force of nonstructural element.
Simple 3, 10, and 30-story buildings with a nonstructural element which is located at roof or near the middle of the building height are selected. Based on 2009 Korean Building Code, the seismic design force applied at the nonstructural element is evaluated. Response spectrum analysis is conducted with the design response acceleration spectrum of 2009 Korean Building Code and the analytical response is compared with the seismic design force from the Code. Furthermore, an artificial earthquake based on Korean design response acceleration spectrum and the 50% intensity of El Centro earthquake, which can be considered as the maximum future earthquake possibly occurring in Korea, are selected to conduct time history analysis. When the period of the nonstructural element is shorter than 0.06 second or longer than that of the 1st period of each building, the Code equations of seismic design force for nonstructural element seems to be appropriate. However, the period of the nonstructural element is close to the one of the building's higher mode periods including the 1st period, seismic force of the nonstructural element might exceed the Code specified seismic design force.
The seismic damage of non-structural components, such as communication facilities, causes direct economic losses as well as indirect losses which result from social chaos occurring with downtime of communication and financial management network systems. The current Korean seismic code, KBC2009, prescribes the design criteria and requirements of non-structural components based on their elastic response. However, it is difficult for KBC to reflect the dynamic characteristics of structures where non-structural components exist. In this study, both linear and nonlinear time history analyses of structures with various analysis parameters were carried out and floor acceleration spectra obtained from analyses were compared with both ground acceleration spectra used for input records of the analyses and the design floor acceleration spectrum proposed by National Radio Research Agency. Also, this study investigates to find out the influence of structural dynamic characteristics on the floor acceleration spectra. The analysis results show that the acceleration amplification is observed due to the resonance phenomenon and such amplification increases with the increase of building heights and with the decrease of structure’s energy dissipation capacities.
후설치앵커는 굳은 콘크리트 부재에 설치되어 구조 부재간의 하중 전달 또는 비구조요소의 하중을 구조부재로 전달하는데 사용된다. 국내 후설치앵커는 2007년 콘크리트구조기준 개정에 처음 신설되었으며 기계식 후설치앵커의 설계법만 규정하였다. 2018년 10월 기준 개정에서는 부착식 후설치앵커 설계법도 추가되었으며 특히 부록에서 본문 22장으로 이동하였다. 2020 년 국가건설기준으로 반영되면 법적 기준의 지위를 갖게된다. 내진보강, 구조보강, 증축 및 리모델링을 비로한 구조 요소간 접합뿐 아니라 기계전기설비와 마감재 등 비구조요소를 구조부재에 연결에도 후설치앵커가 많이 사용된다. 이 연구에서는 구조기준의 개정사항을 분석하여 안전하고 경제적인 후설치앵커 설계방법을 제시하고자 한다.
세계적으로 지진과 같은 자연재해로 인한 대규모 피해가 증가하고 있다. 다양한 연구를 통하여 건물에 대한 내진성능은 확보되었으나, 비구조요소의 내진성능 확보 미흡으로 인하여 인명 피해 및 경제적 손실이 발생하고 있다. 비구조요소는 구조물에 설치되는 위치가 다양하고, 구조물의 위치에 따라 발생하는 진동특성이 다르므로 구조물의 위치별 응답스펙트럼이 필요하다. 또한 구조물의 형식과 구조물이 설치되는 위치에 따라 구조물에 발생하는 응답스펙트럼이 다르게 발생한다. 따라서 응답스펙트럼의 선정이 중요하므로 비구조요소에 작용하는 응답스펙트럼을 도출할 수 있는 명확한 방법이 필요하다. 본 논문에서는 응답스펙트럼을 도출하는 방법을 제안하였으며, 제안한 방법으로 국내에서 발생 가능한 지반응답스펙트럼과 구조시스템을 선정하여 구조해석을 수행하였다. 또한, 간단한 수식으로 응답스펙트럼을 도출하는 방법을 제안함으로서, 비구조요소의 내진시험에 필요한 응답스펙트럼을 생성할 수 있도록 하였다.
Interest and requirement of seismic qualification for nonstructural components are increasing in South Korea after observing nonstructural component failures by Kyungju earthquake on 12, October, 2016. However, amplification of input motion by hight of building are not considered in most of seismic qualification or design for nonstructural components in South Korea. In this study, seismic loads are compared which is applied to seismic qualification or design for structural or nonstructural component. As a result, amplification effect by vertical location in a building for nonstructural component should be considered for efficient seismic qualifications. Also, further studies are needed how to apply those amplification effects to required response spectra.