PURPOSES : This study focuses on how quickly emergency alarm facilities recognize a fire, respond to evacuation behavior, and induce appropriate behavior in response to the fire alarm sound by listening to the fire alarm sound from a sound device. METHODS : Prior research on alarm sounds affecting evacuation behavior was identified, and a subjective evaluation of alarm sounds was conducted to study the most appropriate evacuation-inducing behavior for alarm sounds. In the event of a fire, a subjective evaluation of the sound pressure level and frequency analysis of the sound system, which affects the occupants in the building, were conducted to analyze the type of alarm sound and evacuation behavior. RESULTS : As a result of the subjective evaluation of the occupants’ listening risk, there was little cognitive response to the change in sound pressure level according to frequency. It was found that the alarm sound could give a sense of crisis or tension owing to the difference in sound pressure level change according to the change in time difference. CONCLUSIONS : In conclusion, with high sound pressure and large decibel deviation, the evacuation behavior of respondents after education was more active in the wake-up call that made a sound that seemed to be torn.
The people who are in the noise factory are difficult to hear and recognize about fire and to evacuate quickly when a fire occurs. This study was conducted to analyze workplace’s background noise of 31 factories in Incheon and to know the workplace noise level comparing to fire alarm sound level. The measured average noise level was 96.8dB(A). Noise level of measured result was exceeded as 6.8dB(A) comparing to NFSC (National Fire Safety Code) noise level of 90dB. NFPA suggests that when background noise exceeds 85dB or more than that, other methods should be considered to know alarm sound. Also fire alarm sound should exceed more than 15dB(A) comparing to background noise level. Therefore it was concluded that the design of the fire alarm systems should not be applied to the workplace without considering background noise and it needs to be improved with regulations and the systems.
본 연구에서는 인천광역시의 37개 사업장(공장)을 대상으로 작업현장의 소음을 측정 및 분석하여 소음이 화재경보음 인지에 미치는 영향을 분석하였다. 측정결과 평균소음이 95.8dB(A)나왔다. 이는 국내 경보장치 음량기준(화재경보음 발생장치에서 1m떨어진 곳에서 90dB이상)보다 5.8dB(A)높게 나왔다. 미국방화협회(NFPA)에 따르면 암소음(기기음)이 85dB(A)이거나 이상일 경우 화재경보음 인지정도가 미흡하기 때문에 다른 방법을 강구하도록 되어 있다. 또한 화재경보음은 암소음보다 15dB(A) 높아야 한다고 하고 있다. 따라서 주변의 환경을 무시한 획일적인 화재경보음 설계에 대해서 제도적 및 법적 개선이 필요하다고 사료된다.
대한민국의 급격한 경제 발전은 도심 빌딩의 고층화, 산업현장의 공장 대규모화로 이어졌다. 하지만 소방안전에 대한 투자와 인식이 미흡하여 고층 빌딩과 공장 등에 대형화재로 인해 대규모 인명피해와 재산피해가 발생되고 있다.
공장(사업장)의 경우는 생산설비를 가동하기 위해 많은 유틸리티 설비들을 보유하고 있다. 이에 대표적인 유틸리티 설비로는 공기압축기, 냉동기, 보일러, 모터펌프 등이 있다. 이러한 설비들은 기기음(암소음)을 많이 발생하기 때문에 화재 발생 시 화재경보음이 재실자에게 전달되기란 매우 힘든 실정이다. 또한 대부분의 공장시설에는 복도에 화재경보설비가 위치하고 있고 기기실에는 출입문이 설치 되어있기 때문에 재실자에게 경보전달이 이루어지기가 더욱 힘든 실정이다. 특히 재실자의 업무 집중도에 따라 경보음 인지정도에 많은 차이가 발생될 것이다. 이러한 경보음의 전달 문제점을 연구하기 위해 실제 상황을 묘사하여 경종의 형식승인 및 검정기술기준·시험세칙(KOFEIS 0305)과 미국방화핸드북(Fire Protection Handbook)의 측정기준 및 예시기준에 따라 조건별로 실험하였다. 실험결과 기기실문을 닫은 상태에서 기기음에 노출될 경우 대부분의 피험자가 화재경보음을 인지하지 못하였다. 미국방화협회(NFPA)에서는 암소음이 85dB이거나 이상일 경우 다른 경보방법을 강구하도록 되어있다. 따라서 기기음과 장소의 특성을 고려하지 않는 일률적으로 화재경보음 설계시공에 대한 제도적 개선이 요구되는 결론을 도출하였다.