PURPOSES : This study aimed to secure the work space in alarm valve rooms to ensure stable working conditions for the engineers. METHODS : We analyzed situations where alarm valve room work spaces were inadequately secured posing a problem. Using the Ovako working posture analysis system (OWAS) method, we measured the body size of adult male technicians and their tools to analyze the actual space needed for them to maintain a healthy posture while working. On this basis, we proposed regulations governing workspace size and acceptable durations for unstable body postures. RESULTS : By measuring valve room work space and technician body size, we found that the workspace was inadequate for technicians. Applying OWAS showed that securing more space in the valve room improved the construction stability. CONCLUSIONS : Regulations on valve room size and appropriate work space for technicians will improve construction and inspection stability. This reduces the probability of poor construction and inadequate inspection, increasing the reliability of the firefighting facility system.
PURPOSES : Sprinkler facilities play a crucial role in extinguishing fires in the early stages of a building blaze. Data indicate that more than 96% of fires are suppressed by sprinklers before growing out of control. However, corrosion and pitting of the sprinkler piping can reduce system performance as facilities age. The purpose of this study is to develop an eco-friendly water-soluble corrosion inhibitor to improve the reliability and longevity of sprinkler piping. METHODS : This study compared and analyzed silicate-based sprinkler piping shrinkage agents as corrosion inhibitor against existing commercial options. Tests were conducted to evaluate reactivity with fire extinguishing water, including electrolyzed reduced water and normal water. The anticorrosive performance of the silicate-based corrosion inhibitor was evaluated under various conditions to establish suitability before potential development or commercialization. RESULTS : The new corrosion inhibitor demonstrated eco-friendly performance. In testing, none of the primary four hazardous substances that pose the most risk of harm to the human body (specifically, arsenic (As), lead (Pb), cadmium (Cd), and mercury (Hg)) were detected. The inhibitor effectively reduced corrosion of carbon steel (SPP), with weight loss rates averaging 0.12% and not exceeding 0.27%. For copper (CDA 110) weight loss rates were up to 0.03%. Testing under constant temperature and humidity conditions show that the inhibitor kept weight loss was below 0.002 g, with no significant numerical value for the weight loss rate. Overall, the results indicate the potential for an environmentally-safe corrosion inhibitor. CONCLUSIONS : The optimal silicate-based sprinkler system can provide real-time sensor information such as oxygen saturation, pH concentration, and total dissolved solids (TDS). These metrics are closely related to the aging process. By linking this system with an aging monitoring solution, maintenance costs and safety could be improved over the lifespan of the sprinkler system. The sensors and monitoring capabilities are expected to enhance maintenance efficiency and equipment reliability.
스프링클러설비에서 누수 하자가 발생되면 설비의 작동을 멈추는 경향이 많고 이는 입주자의 안전에 많은 지장을 초래하게 되며, 누수피해로 재산상의 손실도 발생하게 되므로 스프링클러설비는 화재진압 성능뿐만 아니라 내구성도 높아야 할 것이다. 동관 부식은 스프링클러설비 배관에서 주로 나타나는 특이한 현상으로서 그 동안 제시된 여러 학설들과 법원의 판단 등을 종합하여 검토한 결과, 동관의 부식은 매우 복합적인 요인에 의해 발생되고 있고, 하자보수 방법의 결정요인의 핵심은 보완시공을 통한 부식억제의 가능성 여부를 판단하는 것인데 실증적용 사례 연구 등을 통한 결론을 도출 하였다. 또한 스프링클러설비의 설비의 내구성 강화에 대한 법규적 미비점에 대해서도 연구를 통한 개선방안을 제시하여 향후 하자발생을 줄이고자 하였다.
A fire sprinkler system is very important to extinguish fire in the building. The sprinkler system initiates sprinkler discharge if the detection system identifies a developing fire and opens the pre-action valve. However, pre-action fire sprinkler systems mainly installed in the underground parking lot at the apartment complex do not properly operate at fire if the connection type of fire sprinkler systems does not properly installed and operated. This study identified the relationship between fire dispersion & damage and the connection type of water supply in the sprinkler system from many fire cases at the apartment complex in South Korea. In addition, this study also identified the water supply differences and characteristics between South Korea and foreign countries. The main purpose of this study is also to improve the water connection types in the sprinkler system that can reduce the potential failures of pre-action valve operation through electrical signal system. The study also suggests the improvement plan for water connection types in pre-action fire sprinkler system that can minimize potential failure of pre-action fire sprinkler system. The suggestions for revising the fire safe standard in South Korea includes letting the water supply pipe of sprinkler system water inlet connect to the second side of pre-action valve and the water flow device that can minimize potential failure of sprinkler system.
본 연구는 스프링클러식 관개에서 관비재배가 대추 유목의 생육 및 토양 화학적 특성에 미치는 영향에 대하여 알아보고자 수행하였다. 2012년에 1년생 대추나무를 시험포장에 식재하고 2012년부터 2013년까지 시험을 수행하였다. 시험처리는 토양검정 추천 시비량을 기준으로 관비 50%, 관비 75%, 관비 100%, 관비 125%, 관비 150%와 고형 비료 100%처리를 두었다. 대추나무의 줄기 길이 및 줄기 직경은 관비 125% 및 150%에서 가장 좋았다. 8월에 채취된 대추나무 잎의 T-N, P, K, Ca 및 Mg의 함량은 각각 21.7~ 25.5 g/kg, 1.97~ 2.10 g/kg, 26.8~ 30.5 g/kg, 7.64~ 8.71 g/kg, 2.31~ 3.05 g/kg 범위에 있었다. T-N, P, K 및 Mg함량은 8월에 채취된 잎에서 10월에 채취된 잎 보다 많았다. 2013년 시험후 토양은 시험전 토양에 비하여 pH는 낮아지고 EC, 질산태 질소 및 치환성 칼륨은 다소 높아졌다.
The numerical calculation was carried out using OmniCADDⓇ HCS Hydraulic Calculation Software to certify if flow velocities in pipes reduced in diameter were satisfied with fire codes for a dry system of underground parking area in apartment complex. The design pressure and flow rate for the dry system were 4.3 bar and 1633.8 lpm. The maximum discharge pressure and flow rate of sprinklers were 2.2 bar and 118.2 lpm. The maximum flow velocities in main pipe, branch line and other pipe of the dry system were 1.5 m/s, 5.0 m/s and 3.5 m/s. The design propriety could be clearly certified by satisfying with fire codes related to flow velocities for the pipe network of the dry system.
본 연구는 하향 분사식 미니스프링클러의 낙수방지를 위한 새로운 제안으로 패킹부를 구성하여 패킹과 패킹지지부, 패킹 연결지지체의 메카니즘 분석과 구조 해석을 통하여 패킹부 소재 선정의 타당성을 확인하여 하향 분사식 미니스프링클러의 낙수방지 메카니즘을 개발하고, 제품을 제작하여 살수특성 실험을 수행한 결과는 다음과 같다. 낙수방지를 위하여 삽입되는 패킹부의 재료는 구조해석결과, 압력변화에 대응할 수 있는 재질로서 패킹재는 천연고무(ASTM; NR), 패킹지지체는 폴리프로필렌(PP)이 적합함을 확인하였다. 성능시험 결과, 미니스프링클러의 접속관에 용수를 공급할 때와 중단되는 과정의 대기압과 평형상태에서 선정된 패킹 및 패킹지지체는 압력제어 기능을 정확히 수행하여 낙수가 거의 발생하지 않고, 압력변화에도 민감하게 대응함을 확인하였다. 작용압력별 살수특성 성능을 분석한 결과, 유효살수반경, 유효살수면적, 평균살수심, 최대살수심, 유효최대살수심은 작용압력이 증가함에 따라 모두 증가하는 것으로 나타났다. 살수높이별 살수특성 성능을 분석한 결과, 유효살수반경과 유효살수면적은 살수 높이가 0.2m일 때 가장 낮은 값을, 0.3m일 때 가장 높은 값을 보였고, 그 이상 살수 높이가 높아지면 반대로 감소하였으며, 평균살수심은 살수높이가 높아질수록 감소하였다. 제안된 하향 분사식 미니스프링클러는 패킹부의 영향으로 압력이 증가함에 따라 살수성능이 유연성 있게 변화하여 급격한 변화를 나타내지 않았고, 용수압력이 감소될 때에는 작용압력이 1.1kgf/cm2이상의 범위에서만 살수되었으며, 그 이하에서는 제안된 패킹부에 의해 하향 분사식 미니스프링클러 본체로 공급되는 용수가 차단되어, 대기압과 평형상태에 있는 물의 자중과 중력작용에 의한 자유낙하를 방지함으로서 물방울의 형성 및 낙수 발생의 예방을 확인하였다.
The trends in building construction these days are moving towards having better work spaces and greater suitability for the use of information technology. Therefore people can work in a more relaxed delightful and pleasant environment. Accident such as like fire could cause the mass destruction of human beings. This paper aims to evaluate the path of the spread of a fire and the suitability of fire fighting appliances for maximum egress time. General advanced phase of compartment. Aswell, we analyzed and verified the path of the flame in compartment fires. Also we conducted an analysis of the adaptation of sprinkler systems concerned with sprinkler RTI. Moreover those evaluation is made more earlier by the development and use of computer simulation program and rapid progress to apply PBFD (Performance Based Fire Design).
구조와 크기가 각각 다른 12종의 미니 스프링클러를 대상으로 살수입자의 크기에 대한 분두의 구경과 살수압력의 영향을 조사하고 스프링클러 종류별로 각 살수 도달거리에서의 살수입자의 크기를 실험한 결과 다음과 같은 결과를 얻었다. 액분산기를 갖은 미니 스프링클러 살수입자 크기와 분두 구경과의 관계를 분석한 결과, 살수입자의 크기는 스프링클러의 분두 구경 보다는 스프링클러의 구조 특히 액분산기의 형태에 더 큰 영향을 받는 것으로 나타났다. 살수압력이 살수입자의 크기에 미치는 영향을 분석한 결과 살수입자의 크기는 살수압력의 1/3승에 반비례함이 확인되었다. 따라서 임의 압력하에서 살수되는 스프링클러 살수입자의 크기는 특정 압력하의 실험결과로부터 용이하게 예측할 수 있다. 살수입자 도달거리와 살수입자 크기와의 관계는 살수입자 도달거리의 2차 함수에 비례하여 살수입자의 크기가 증가하는 것으로 분석되었다. 시판되고 있는 미니 스프링클러의 대표적인 종류를 이용하여 실험한 스프링클러의 살수입자 도달거리별 살수입자의 크기는 스프링클러 종류에 따라 상당한 차이가 있으나 대체적 크기를 보면 도달거리 1m 이내에서는 100~300μm, 도달거리 1m~2m 범위에서는 230~470μm, 도달거리 2~3m 범위에서는 300~770μm으로 나타났다.
분구의 구경과 액분산기의 구조가 각각 다른 12종의 미니스프링클러를 대상으로 살수량과 살수강도분포를 실험하여 얻은 주요 결과는 다음과 같다. 미니 스프링클러의 살수량은 분구의 이론 유출량 산출 수식에 의해 예측할 수 있었다. 실험한 스프링클러의 유량계수는 분구구경 증가에 따라 감소하여 그 크기는 분구구경 0.8, 1.2, 1.6mm의 경우 각각 0.90-30.95, 0.80-0.82, 0.76-0.79의 범위로 나타났다. 스프링클러의 살수 분포는 동일한 구조의 스프링클러의 경우 분구구경이 작을 수록 그리고 살수압력이 낮을 수록 균일한 것으로 나타났다. 이러한 스프링클러의 살수분포는 분구구경이나 살수압력 외에도 액분산기의 구조에 따라 크게 영향을 받으므로 액분산기의 구조를 변화하므로서 살수입자의 최대 도달거리나 살수의 균일도를 높일 수 있음을 알 수 있었다.
밤나무림내에 sprinkler system을 고정 설치하고, 이를 이용하여 적정한 시기에 일시에 그리고, 간편하게 약제를 살포함으로써 밤나무의 주요해충인 밤나무흑벌(Dryocosmus kuriphilus)의 피해를 효과적으로 방제할 목적으로 2003년부터 2년간 경남 산청군 신안면에서 본연구가 수행되었다. 공시약종은 carbaryl 50% WP, 1,500배액을 사용하였으며, 얻어진 결과는 다음과 같다. 밤나무흑벌 성충의 우화시기는 6월 중순부터 7월 중순까지 약35일간이며, 우화최성기는7월상순의 약 5일간이었다. 밤나무흑벌의 우화 및 산란시기에 Carbaryl 50% WP 1,500배액의 수관살포는 밤나무흑벌에 탁월한 방제효과가 있었다. 즉 매일살포구의 평균 충영형성율은 3.0%, 2일간격 살포구의 평균 충영형성율은 12.8%로서 이들은 무처리구의 평균충영형성율 82.9%와 비교하여 각각 96.4% 및 84.5%의 높은 방제효과가 인정되었으며 수관부위별로는 차이가 없었다.
In order to prevent cones from being damaged by cone insects, Gravitarmata margarotana and Dioryctria abietella, sprinkler system was installed on the Pinus koraiensis Seed Orchard. Such a test was conducted at Chung-ju, Chungcheong buk-do, Korea in 2002. Insectides of Diflubenzuron 25% WP ×2,500 and Cyfluthrin 2%EC × 1,000 were sprayed at fifteen-day and twenty-day intervals during the period of insects adult occurrence by sprinkler system. The Gravitarmata margarotana generally emerged for about 53 days from middle April to early June, and peak emergence was 10 days from April 20 to April 30. Dioryctria abietella generally emerged for about 108 days from late April to early August, and peak emergence was 10 days from May 20 to May 30. Damage rate of cones were 8.7~9.7% and 10.9~12.7% on average with crown insecticide spraying with Cyfluthrin and Diflubenzuron, while 67.5% when not treated. Control effectiveness of this insecticide spraying was 85.6~87.1% and 83.9%와 81.2%, respectively. When it considers the forest environment, it is recommended diflubenzuron which is low toxic pesticide. In conclusion, effectual times and number of diflubenzuron 25% WP application with sprinkler system against cone insects were from early May through late August and six times at twenty-day interval.